1 setting an slc address for a single point module, Setting an slc address for a single point module – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 32

Advertising
background image

32

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

Installation

5.2.1 Setting an SLC address for a Single Point Module

Each module can be set to one of 159 addresses (01-159) and is factory preset with an address of
“00”.

To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired
address. The module below is set at “35”. When finished, mark the address on the module face in
the place provided.

NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS-
9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, and MS-
9600UDLS can support module addresses 01 - 159. The plastic stop located on the Tens switch
must be removed to set addresses above 99.

TENS

8 9

10

11

12

13

14

15

0

1

2

3

4

5

6 7

ONES

8 9

0

1

2

3

4

5

6 7

Breakaway Tab - Modules come with

a raised breakaway tab on the TENS

rotary switch. This tab must be

removed when the module is on an

FACP that uses more than 99
addresses.

S

L

C-

seta

dd

.cdr

,S

LC-

seta

d

dt

pH.wm

f, S

L

Cbr

kta

bs.

w

m

f

Dual monitor modules: On dual monitor modules, only even
numbers appear on the ONES rotary switch. The module takes
both the selected address and the next-higher address.

Modules with

Rotary Switches

in vertical

position

Modules with Rotary

Switches in

horizontal position

Figure 5.7 Setting an SLC Address on a Single Point Module