5 mdf-300 wiring diagrams, 1 wiring a nfpa style b idc with an mdf-300, Mdf-300 wiring diagrams – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 39: Wiring a nfpa style b idc with an mdf-300

Advertising
background image

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

39

MDF-300 Wiring Diagrams

Monitor Modules

5.5 MDF-300 Wiring Diagrams

Following is a wiring diagrams that depict NFPA Style B (Class B) Initiating Device Circuits
(IDCs) using MDF-300 Dual Monitor Modules.

5.5.1 Wiring a NFPA Style B IDC with an MDF-300

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Use the rotary switches on the module to set it to the SLC address. Each dual module takes two
addresses on the SLC. Circuit ‘L’ corresponds to the address set on the rotary switches, which will
be an even number. Circuit ‘H’ will automatically respond to the next higher address, which will be
an odd number. Use caution to avoid duplicate addressing of modules on the system. Refer to “Set-
ting an SLC address for a Single Point Module” on page 32.

Each IDC (H & L) is power limited to 230 microamperes @ 24 VDC.

The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MDF-300-10 module.

Refer to the Device Compatibility Document for compatible smoke detectors.

See “Power Considerations” on page 61 for information on supervising 24 VDC power.

T11
T10
T9
T8
T7
T6

T1
T2
T3
T4
T5

S

L

C

-id

cB3

fdm

1t

ph.

w

m

f

Heat
Detector

Manual
Pull
Station

SLC

MDF-300

Base +1 Address
(IDC Circuit H)

Base Address
(IDC Circuit L)

47K
ELR

47K
ELR

Manual
Pull
Station

Figure 5.14 Typical Style B IDC Wiring with an MDF-300