4 control panel terminal blocks, 1 ms-9200, 2 ms-9600, ms-9600ls, & ms-9600udls – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 18: Control panel terminal blocks, Ms-9200 2.4.2: ms-9600, ms-9600ls, & ms-9600udls

Advertising
background image

18

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Wiring Requirements

Control Panel Terminal Blocks

2.4 Control Panel Terminal Blocks

The terminal blocks on the control panel circuit board that concern the SLC circuit are described
below. For more information on this subject refer to the control panel’s Instruction Manual.

2.4.1 MS-9200

TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable.

TB6 provides connections for the SLC wiring.

198 addresses are available per loop (99 detectors and 99 modules).

2.4.2 MS-9600, MS-9600LS, & MS-9600UDLS

TB3 provides two types of 24 VDC power; Nonresettable and Resettable.

TB8 provides connections for the SLC wiring.

198 addresses are available per loop (99 detectors and 99 modules) while operating in CLIP mode.
318 addresses are available per loop (159 detectors and 159 modules) while operating in LiteSpeed
mode.

TB6

SHIELD

SLC

SLC

TB4

SL

C

-9

200

tb

.wmf

SLC
Return

SLC Out

Connections for wire shield

Unregulated Power

Nonresettable Power

Resettable Power

Figure 2.6 MS-9200 Terminal Blocks

TB8

SHIELD

SLC

SLC SLC SLC

TB3

SLC Return

SLC Out

Connections for
wire shield

Nonresettable
Power

Resettable Power

S

L

C

-960

0t

b.w

m

f

Figure 2.7 MS-9600 Series Terminal Blocks