6 mmf-302 wiring diagrams, 1 wiring a nfpa style b idc with an mmf-302, Mmf-302 wiring diagrams – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 40: Wiring a nfpa style b idc with an mmf-302

Advertising
background image

40

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Monitor Modules

MMF-302 Wiring Diagrams

5.6 MMF-302 Wiring Diagrams

Following are wiring diagrams that concern NFPA Style B (Class B) and D (Class A) Initiating
Device Circuits (IDCs) using MMF-302 Zone Interface Modules.

5.6.1 Wiring a NFPA Style B IDC with an MMF-302

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.

The IDC is supervised and power limited to 230 microamperes @ 24 VDC.

The figure below shows typical wiring for a supervised and power-limited NFPA Style B IDC
using an MMF-302 module.

Refer to the Device Compatibility Document for compatible smoke detectors.

24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.

See “Power Considerations” on page 61 for information on 24 VDC power.

SLC

IDC

SL

C-

id

cB

2tp

H

.w

mf

MMF-302

Two-wire
smoke
detectors

3.9K ELR
(supplied with module)

24 VDC Resettable power.

90 mA External 24 volt

supply required

Figure 5.15 Typical Style B IDC Wiring with an MMF-302