Installation

Monitor Modules

5.1.3 Dual Monitor Module

MDF-300 Module

The MDF-300 is similar to the MMF-300 but provides for two independent 2-wire IDCs at two
separate, consecutive addresses.

5.1.4 Mini Monitor Module

MMF-301 Monitor Module

The MMF-301 is functionally and electrically identical to an MMF-300, but is offered in a smaller
package for mounting directly in the electrical box of the Style B (Class B) device being monitored.

5.2 Installation

When installing any of these modules DO NOT mix the following services that the IDC provides:

Fire alarm service

Automatic and manual waterflow alarm service with normally open contact devices

Sprinkler supervision with normally open contact devices