FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Control Modules

CMF-300-6 Installation

6.4.6 Features Not Supported

The “Synchronization” and “Power Supply Monitoring” features are not supported at this time.

6.4.7 Circuit Board Information

CMF

-30

0-

6.

wmf

Synchronization Generator -
Not Supported. DO NOT
remove shunts.

Power Supply Monitors -
Not Supported. DO NOT
remove shunts.

Disable Address -

Place shunt onto required pins.

Select

Style Y (Class B) or

Style Z (Class A) -

Remove shunt for Style Z (Class A).

Short Circuit Protection - Remove
shunt from the corresponding pins to
enable. Shunt #1 for first address, #2
for second address, etc.

#1 #2 #3 #4 #5 #6

SLC Address
Set rotary switches to
address required.

Status Indicators
Green LEDs are
controlled by FACP to
indicate status of each
module address.

Figure 6.4 CMF-300-6 Control Module Settings