MMF-302 Wiring Diagrams

Monitor Modules

5.6.2 Wiring a NFPA Style D IDC with an MMF-302

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).

Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to “Setting an SLC address for a Single Point Module” on page 32.

The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-302 module.

Refer to the Device Compatibility Document for compatible smoke detectors.

24 VDC power must be provided from a UL listed power supply for fire protection use. This
power is inherently supervised by the module.

See “Power Considerations” on page 61 for information on 24 VDC power.

SLC

Two-wire
smoke
detectors

3.9K ELR
(supplied with module)

IDC

MMF-302

S

LC-

idcD

2tpH

.w

mf

24 VDC Resettable power.
90 mA External 24 volt supply required

Figure 5.16 Typical Style D IDC Wiring with an MMF-302