4 nfpa style 7 slc using isolator modules, Nfpa style 7 slc using isolator modules – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 26

Advertising
background image

26

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

SLC Circuits with Isolators

NFPA Style 7 SLC Using Isolator Modules

4.4 NFPA Style 7 SLC Using Isolator Modules

Style 7 operation requires using isolator modules (or a combination of isolator modules and isolator
bases) before and after each device. Flanking each device with an isolator provides fault protection
to all other devices on the loop.

T-tapping is NOT allowed within the Style 7 wiring configuration.

When a detector base or pull station is used, install isolator modules on both sides of the
device.

Connections between isolator modules and the device they isolate must be “close-nippled”
conduit, within 3 feet (91.44 cm).

2

1

3

4

3

4

3

4

1

3

1

3

2

1

2

1

S

LC

-style7

iiso

.wmf

SLC Out

SLC Return

Two-Wire
Addressable
Detector

Addressable

Pull Station

Control Panel

Two-wire

Addressable

Detector

Figure 4.4 NFPA Style 7 SLC Using Isolator Modules

Isolator
Module

Isolator
Module

Isolator
Module

Isolator
Module

Isolator
Module

Isolator
Module

Isolator
Module

Isolator
Module