3 wiring an isolator base, 4 wiring a relay base, Wiring an isolator base 9.2.4: wiring a relay base – Fire-Lite SLC Intelligent Control Panel Wiring Manual User Manual

Page 58

Advertising
background image

58

FireLite SLC Wiring Manual — P/N 51309:P1 10/12/2011

Intelligent Detector Bases

Installation and Wiring

9.2.3 Wiring an Isolator Base

The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC con-
nected at terminals 2 and 3. It will not isolate its installed detector from short circuits that occur on
the SLC connected at terminals 1 and 2. In Style 7 applications, the loss of a single detector during
a short circuit is not acceptable, and an isolator module must be installed as shown in the figure
below.

9.2.4 Wiring a Relay Base

Figure 9.3 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.

+

+

SLC Out

SLC In

Conduit

I300 Isolator Module

sl

c-

22

4b

i2

w

ire

.w

m

f

Figure 9.2 Wiring of a B224BI Isolator Base Mounting Plate

Note: The “grid” pattern on the
redesigned B224BI mounting
plate has been removed for
illustration purposes only.

+ -

+ -

sl

c-

b

22

4

rb

2

w

ir

e.

w

m

f

Figure 9.3 Wiring of a B224RB Relay Base Mounting Plate

To next device

on SLC

SLC

Normally Closed
Common
Normally Open

Note: The “grid” pattern on the
redesigned B224RB mounting
plate has been removed for
illustration purposes only.

Advertising