KYORITSU 6305 Instruction Manual User Manual

Page 103

Advertising
background image

KEW6305

8.6

● Saving Demand values

Demand values will be saved at the preset interval (Setting 09).
Final demand value is determined at the end of every demand measurement cycle (Setting 16), and will
be reset automatically. The maximum demand value measured during every demand cycle will be held
and displayed on the LCD together with the time and date information.

The following is an example of the saving status of a demand value survey where the demand interval is
10 min, demand cycle is 30 min and the survey duration is about 3 hours.

Demand value(kW)

Demand measure-ment cycle

Start of demand

End of demand

Demand value

(Present

demand

value)

Max. demand value

displayed on LCD

Data saving point

Demand determined

point

0 0.5h 1h 1.5h 2h 2.5h 3h