3 criteria of judgment – KYORITSU 6305 Instruction Manual User Manual

Page 64

Advertising
background image

5.7

KEW6305

5.4.3 Criteria of judgment

System to be checked

Check item

Criteria of Judgment

3P4W

3P3W3

A

3P3W 1P3W 1P2W-31P2W-21P2W-1

Error

message

Should be 45Hz or more.

Err.Lo_Hz

Frequency

Should be 65Hz or less.

f

Err.Hi_Hz

Should be 60% or more of (V range x
VT ratio).

Err.Lo_V

Voltage

input

Should be 110% or less of (V range x
VT ratio).

V1/V2/
V3

V1/

V2

V1

Err.Hi_V

Voltage

balance

Should be within ±10º of reference
phase.

DEG(V2)
:120°
DEG(V3)
:240°

DEG

(V2)
:300
°

DEG

(V2)
:180

----

Err.PH_V

Voltage

phase

Should within ±20% against V1.

V2/V3 V2

----

Err.bL_V

Should be 10% or more of (A range

x CT ratio).

* One range low if auto-ranging has been

selected.

Err.Lo_A

Current

input

Should be 110% or less of (A range

x CT ratio).

* One range high if auto-ranging has been

selected.

A1/A2/
A3

A1/A2

A1

A2

A3

A1

A2

A1

Err.Hi_A

PFi (absolute value) should be 0.5 or

more.

* for 3P3W3A, 0 < PFi

PF1/
PF2/
PF3

PF1/
PF2

PF
1

PF
2

PF
3

PF
1

PF
2

PF
1

Err.PH_A

Current

phase

Pi should be positive value.

P1/P2/
P3

P1/P2

P1

P2

P3

P1

P2

P1

Err.PH_A

*KEW6305 may show any incorrect connection is found if great power factors (0.5 or less)

exist at the measurement site.