2 setting procedure of each setting item – KYORITSU 6305 Instruction Manual User Manual

Page 30

Advertising
background image

4.3

KEW6305

4.2 Setting procedure of each setting item

“ Setting 01” Wiring system

Following explains how to make settings for wiring system.

Select the appropriate wiring system according to the environment to be measured.

Setting item

1P2W(1ch)

: Single-phase 2-wire (1ch)

1P2W(2ch)

: Single-phase 2-wire (2ch)

1P2W(3ch)

: Single-phase 2-wire (3ch)

1P3W

: Single-phase 3-wire

3P3W :

Three-phase

3-wire

3P3W3A :

Three-phase

3-wire

3P4W :

Three-phase

4-wire

Default value (or after system reset)

3P3W

* Two-wattmeter method should be used for measuring 3P3W that requires using two Clamp sensors.

* For measuring/ recording the voltage and current on each phase, select “3P3W3A” and use three

Clamp sensors.

1 Use the

Cursor

key on the selection screen, and select “Setting 01”.

2 Press the

ENTER

key to get the instrument into setting change mode.

3 Present setting (or default value: 3P3W) blinks. Select the appropriate wiring configuration with the

Cursor

key, and then press the

ENTER

key after making necessary change.