Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 13

Advertising
background image

506724-01

Page 13 of 57

Issue 1108

Return Air -- Horizontal Applications

Return air may be brought in only through the end of a furnace

installed in the horizontal position. The furnace is equipped

with a removable bottom panel to facilitate installation. See

Figure 13.

Filters

This unit is not equipped with a filter or rack. A field provided

filter is required for the unit to operate properly. Table 1 list

recommended filter sizes.

A filter must be in place whenever the is operating.

Duct System

Use industry approved standards to size and install the

supply and return air duct system. This will result in a quiet

and low-static system that has uniform air distribution.

NOTE: This furnace is not certified for operation in heating

mode (indoor blower operating at selected heating speed)

with an external static pressure which exceeds 0.5 inches

w.c. Operation at these conditions may result in improper

limit operation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable

access panel should be installed in the supply air duct. The

access panel should be large enough to permit inspection

(by reflected light) of the heat exchanger for leaks after the

furnace is installed. The furnace access panel must always

be in place when the furnace is operating and it must not

allow leaks into the supply air duct system.

Return Air Plenum
NOTE: Return air must not be drawn from a room where

this furnace, or any other gas fueled appliance (i.e., water

heater), or carbon monoxide producing device (i.e.,

wood fireplace) is installed.

When return air is drawn from a room, a negative pressure

is created in the room. If a gas appliance is operating in a

room with negative pressure, the flue products can be pulled

back down the vent pipe and into the room. This reverse

flow of the flue gas may result in incomplete combustion

and the formation of carbon monoxide gas. This raw gas or

toxic fumes might then be distributed throughout the house

by the furnace duct system.

Return air can be brought in through the bottom or either

side of the furnace. If a furnace with bottom return air is

installed on a platform, make an airtight seal between the

bottom of the furnace and the platform to ensure that the

unit operates properly and safely. Use fiberglass sealing

strips, caulking, or equivalent sealing method between the

plenum and the furnace cabinet to ensure a tight seal. If a

filter is installed, size the return air duct to fit the filter frame.

Pipe & Fittings Specifications

All pipe, fittings, primer and solvent cement must conform

with American National Standard Institute and the American

Society for Testing and Materials (ANSI/ASTM) standards.

The solvent shall be free flowing and contain no lumps,

undissolved particles or any foreign matter that adversely

affects the joint strength or chemical resistance of the

cement. The cement shall show no gelation, stratification,

or separation that cannot be removed by stirring. Refer to

Table 2 for approved piping and fitting materials.

INTAKE PIPE

*GAS

CONNECTOR

SERVICE PLATFORM

*Gas connector may be
used for Canadian
installation if accept-
able by local authority
having jurisdiction.

EXHAUST PIPE

FIGURE 17

RAISED

PLATFORM

TABLE 1

Furnace

Cabinet Width

Filter Size

Side Return

Bottom Return

17−1/2"

16 X 25 X 1 (1)

16 X 25 X 1 (1)

21"

16 X 25 X 1 (1)

20 X 25 X 1 (1)

24−1/2"

16 X 25 X 1 (2)

24 X 25 X 1 (1)

Advertising
This manual is related to the following products: