Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 29

Advertising
background image

506724-01

Page 29 of 57

Issue 1108

5. On field supplied terminations for sidewall exit, exhaust

piping may extend a maximum of 12 inches (305 mm)

for 2” PVC and 20 inches (508 mm) for 3” (76 mm) PVC

beyond the outside wall. Intake piping should be as

short as possible. See Figures 31 and 33.

6. On field supplied terminations, a minimum distance

between the end of the exhaust pipe and the end of the

intake pipe without a termination elbow is 8” and a

minimum distance of 6” with a termination elbow. See

Figures 31 and 33.

7. If intake and exhaust piping must be run up a side wall

to position above snow accumulation or other

obstructions, piping must be supported every 24” (610

mm) as shown in Figures 31 and 33. When exhaust

and intake piping must be run up an with pipe sized per

Table 6. The intake piping may be equipped with a 90°

elbow turndown. Using turndown will add 5 feet (1.5 m)

to the equivalent length of the pipe.

8. A multiple furnace installation may use a group of up to

four terminations assembled together horizontally, as

shown in Figure 37.

2" EXTENSION
FOR 2" PVC PIPE
1" EXTENSION
FOR 3" PVC PIPE

FIGURE 34

1−1/2" ACCELERATOR

(

all −45, −070 and −090 units)

FURNACE

EXHAUST

PIPE

FURNACE

INTAKE PIPE

4’’

GLUE EXHAUST

END FLUSH INTO

TERMINATION

FLAT SIDE

FLUSH−MOUNT SIDE WALL TERMINATION

51W11

FIGURE 33

FIELD SUPPLIED WALL TERMINATION

See venting table

5

for maximum venting lengths with this

arrangement.

* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)

2" (51mm)

Vent Pipe

3" (76mm)

Vent Pipe

12" (508MM)

12" (508MM)

6" (152MM)

6" (152MM)

6" (152MM)

12" (305MM)

20" (508MM)

6" (152MM)

6" (152MM)

6" (152MM)

A −Minimum clearance

above grade or average

snow accumulation

B −Maximum horizontal

separation between

intake and exhaust

C −Minimum from

end of exhaust to

inlet of intake

D−Maximum exhaust

pipe length

E −Maximum wall support

distance from top of each

pipe (intake/exhaust)

NOTE − FIELD PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

LARGER VENT PIPE SIZE

TO TERMINATION

D

B

C

SIZE TERMINATION

PER TABLE 6

1/2" (13mm) ARMAFLEX

INSULATION IN UN-

CONDITIONED SPACE

STRAIGHT

APPPLICATION

B

C

D

* WALL

SUPPORT

1/2" (13mm) ARMAFLEX INSULATION

IN UNCONDITIONED SPACE (IF REQUIRED)

E

EXTENDED

APPLICATION

A

A

(IF REQUIRED)