FIGURE 31

FIELD SUPPLIED WALL TERMINATION

See venting table

5

for maximum venting lengths with this

arrangement.

* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)

2" (51mm)

Vent Pipe

3" (76mm)

Vent Pipe

A −Minimum clearance

above grade or average

snow accumulation

B −Maximum horizontal

separation between

intake and exhaust

C −Minimum from

end of exhaust to

inlet of intake

D−Maximum exhaust

pipe length

E −Maximum wall support

distance from top of each

pipe (intake/exhaust)

12" (508MM)

12" (508MM)

6" (152MM)

6" (152MM)

8" (203MM)

8" (203MM)

12" (305MM)

20" (508MM)

6" (152MM)

6" (152MM)

NOTE − FIELD PROVIDED

REDUCER MAY BE

REQUIRED TO ADAPT

LARGER VENT PIPE SIZE

TO TERMINATION

D

B

C

SIZE TERMINATION

PER TABLE 6

1/2" (13mm) ARMAFLEX

INSULATION IN UN-

CONDITIONED SPACE

STRAIGHT

APPPLICATION

B

C

A

D

* WALL

SUPPORT

1/2" (13mm) ARMAFLEX INSULATION

IN UNCONDITIONED SPACE (IF REQUIRED)

E

EXTENDED

APPLICATION

A

(

(IF REQUIRED)