Gas Piping

1. Gas piping may be routed into the unit through either

the left or right hand side. Supply piping enters into the

gas valve from the side of the valve as shown in Figure

49. Move Bellows grommet to side which gas line enters.

Ensure opposite gas line hole is plugged with supplied

plug.

2. When connecting gas supply, factors such as length of

run, number of fittings and furnace rating must be

considered to avoid excessive pressure drop. Table 8

list recommended pipe sizes for typical applications.

NOTE: Use two wrenches when connecting gas piping

to avoid transferring to the manifold.

3. Gas piping must not run in or through air ducts, clothes

chutes, chimneys or gas vents, dumb waiters or elevator

shafts. Center gas line through piping hole. Gas line

should not touch side of unit. See Figures 49 and 50.

4. Piping should be sloped 1/4 “ per 15 feet (6 mm per 5.6

m) upward toward the gas meter from the furnace. The

piping must be supported at proper intervals, every 8 to

10 feet (2.44 to 3.05 m), using suitable hangers or straps.

Install a drip leg in vertical pipe runs to serve as a trap

for sediment or condensate.

5. A 1/8” N.P.T. plugged tap or pressure post is located on

the gas valve to facilitate test gauge connection. See

Figure 57.

6. In some localities, codes may require installation of a

manual main shut-off valve and union (furnished by

installer) external to the unit. Union must be of the

ground joint type.

Leak Check

After gas piping is completed, carefully check all piping

connections (factory and field installed) for gas leaks. Use

a leak detecting solution or other preferred means.

Never use an open flame to test for gas leaks. Check all

connections using a commercially available soap solution

made specifically for leak detection.

The furnace must be isolated from the gas supply system

by closing its individual manual shut-off valve during any

pressure testing of the gas supply system at pressures more

than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).

Compounds used on threaded joints of gas piping must

be resistant to the actions of liquified petroleum gases.

IMPORTANT

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result

in serious injury, death, or property damage. Never use

an open flame to test for gas leaks. Check all

connections using a commercially available soap

solution made specifically for leak detection. Some

soaps used for leak detection are corrosive to certain

metals. Carefully rinse piping thoroughly after leak test

has been completed.

WARNING

If a flexible gas connector is required or allowed by the

authority that has jurisdiction, black iron pipe shall be

installed at the gas valve and extend outside the furnace

cabinet. The flexible connector can then be added

between the black iron pipe and the gas supply line.

CAUTION

Do not exceed 600 in.-lbs. (50 ft.-lbs.) torque when

attaching the gas piping to the gas valve.

WARNING

A low inlet pressure switch in LP/propane applications

is recommended.

IMPORTANT

When testing pressure of gas lines, gas valve must be

disconnected and isolated. See Figure 48. Gas valves

can be damaged if subjected to pressures greater than

1/2 psig (3.48 kPa).

IMPORTANT

FIGURE 48

MANUAL MAIN SHUT−OFF

VALVE WILL NOT HOLD

NORMAL TEST PRESSURE

CAP

FURNACE

ISOLATE

GAS VALVE

1/8" N.P.T.
PLUGGED TAP