Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 38

Advertising
background image

506724-01

Page 38 of 57

Issue 1108

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

Electrostatic discharge can affect electronic

components. Take precautions during furnace

installation and service to protect the furnace’s electronic

controls. Precautions will help to avoid control exposure

to electrostatic discharge by putting the furnace, the

control and the technician at the same electrostatic

potential. Neutralize electrostatic charge by touching

hand and all tools on an unpainted unit surface, such as

the gas valve or blower deck, before performing any

service procedure.

CAUTION

The unit is equipped with a field makeup box. The makeup

box may be moved to the right side of the furnace to facilitate

installation. Seal unused openings on left side with plugs

removed from right side. Secure the excess wire to the

existing harness to protect it from damage.

Refer to Figure 54 for field wiring and Figure 55 for schematic

wiring diagram and troubleshooting.

The power supply wiring must meet Class I restrictions.

Protected by either a fuse or circuit breaker, select circuit

protection and wire size according to unit nameplate.

NOTE: Unit nameplate states maximum current draw.

Maximum Over-Current Protection allowed is 15 AMP.

Holes are on both sides of the furnace cabinet to facilitate

wiring.

Install a separate (properly sized) disconnect switch near

the furnace so that power can be turned off for servicing.

Before connecting the thermostat check to make sure the

wires will be long enough for servicing at a later date. Make

sure that thermostat wire is long enough to facilitate future

removal of blower for service.

Complete the wiring connections to the equipment. Use the

provided unit wiring diagram and the field wiring diagram

shown in Figure 54. Use 18 gauge wire or larger that is

suitable for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in

the absence of local codes, according to the current National

Electric Code (ANSI/HFPA No. 70) for the USA and current

Canadian Electric Code Part 1 (CSA standard C22.1) for

Canada. A green ground wire is provided in the field makeup

box.

NOTE: The gas furnace contains electronic components

that are polarity sensitive. Make sure that the furnace is

wired correctly and is properly grounded.

Accessory Terminals

One line voltage “EAC” 1/4” spade terminal is provided on

the furnace control board. Any accessory rated up to one

amp can be connected to this terminal with the neutral leg

of the circuit being connected to one of the provided neutral

terminals. If an accessory rated at greater than one amp is

connected to this terminal, it is necessary to use an external

relay. See Figure 56 for control board configuration. This

terminal is energized when the indoor blower is operating.

One line voltage “HUM” 1/4” spade terminal is provided on

the furnace control board. Any humidifier rated up to one

amp can be connected to this terminal with the neutral leg

of the circuit being connected to one of the provided neutral

INTERIOR MAKE−UP BOX INSTALLATION

FIGURE 51

MAKE−UP

BOX

Left side

INTERIOR MAKE−UP BOX INSTALLATION

FIGURE 52

MAKE−UP

BOX

Right Side

remove and relocate

plug to unused

opening on left side

Advertising
This manual is related to the following products: