Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 51

Advertising
background image

506724-01

Page 51 of 57

Issue 1108

Service

At the beginning of each heating season, system should be
checked as follows by a qualified service technician:

Blower
Check the blower wheel for debris and clean if necessary.

The blower motors are prelubricated for extended bearing

life. No further lubrication is needed.

The blower access panel must be securely in place when

the blower and burners are operating. Gas fumes, which

could contain carbon monoxide, can be drawn into living

space resulting in personal injury or death.

WARNING

Filters
All air filters are installed external to the unit. Filters should

be inspected monthly. Clean or replace the filters when

necessary to ensure proper furnace operation. Table 1 lists

recommended filter sizes.

Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.

NOTE: After any heavy snow, ice or frozen fog event the

furnace vent pipes may become restricted. Always check

the vent system and remove any snow or ice that may be

obstructing the plastic intake or exhaust pipes.

Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (with

furnace operating). Correct voltage is 120 VAC ± 10%

3. Check amp-draw on the blower motor with the blower

access panel in place.
Motor Nameplate__________Actual__________

ELECTRICAL SHOCK, FIRE,

OR EXPLOSION HAZARD.

WARNING

Failure to follow safety warnings exactly could result in

dangerous operation, serious injury, death or property

damage.

Improper servicing could result in dangerous operation,

serious injury, death, or property damage.

Before servicing, disconnect all electrical power to

furnace.

When servicing controls, label all wires prior to

disconnecting. Take care to reconnect wires correctly.

Verify proper operation after servicing.

Winterizing and Condensate Trap Care
1. Turn off power to the furnace.
2. Have a shallow pan ready to empty condensate water.
3. Remove the clean out cap from the condensate trap

and empty water. Inspect the trap then reinstall the clean
out cap.

Cleaning Heat Exchanger

If cleaning the heat exchanger becomes necessary, follow

the below procedures and refer to Figure 1 when

disassembling unit. Use papers or protective covering in

front of furnace while removing heat exchanger assembly.

1. Turn off electrical and gas supplies to the furnace.

2. Remove the burner access panel.

3. Mark all gas valve wires and disconnect them from

valve.

4. Remove gas supply line connected to gas valve.

5. Remove sensor wire from flame sensor. Disconnect

2–pin plug from the ignitor.

6. Disconnect wires from flame rollout switches.

7. Remove four burner assembly screws at the vestibule

panel and remove gas valve /manifold and burner box

as a single unit.

8. If necessary, clean burners at this time. Follow

procedures outlined in Burner Cleaning section.

9. Remove the clean-out cap on trap and drain. Replace

cap.

10. Disconnect condensate drain line from the condensate

trap. Remove condensate trap (it may be necessary to

cut drain pipe). Remove the 1/2" NPT fitting from the

cold end header box. Disconnect drain tubes from cold

end header collector box.

11. Disconnect condensate drain tubes from flue collar.

Remove screws that secures flue collar in place.

Remove flue collar. It may be necessary to cut the

exiting exhaust pipe for removal of the fitting.

12. Loosen two clamps from flexible no-hub exhaust collar.

13. Disconnect the 2–pin plug from the combustion air

inducer. Remove screws which secure combustion air

inducer to collector box. Remove combustion air

inducer assembly. Remove ground wire.

14. Mark and disconnect all combustion air pressure tubing

from cold end header collector box.

15. Mark and remove wires from pressure switch. Remove

pressure switch. Keep tubing attached to pressure

switch.

16. Remove electrical junction box from the side of the

furnace.

17. Remove blower access panel.

18. Mark and disconnect any remaining wiring to heating

compartment components. Disengage strain relief

bushing and pull wiring and bushing through the hole in

the blower deck.

19. Remove the primary limit from the vestibule panel.

20. Remove top cap screws to allow top cap to be tilted

upward to allow clearance for removing heat exchanger.

Advertising
This manual is related to the following products: