Warning – Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 42

Advertising
background image

506724-01

Page 42 of 57

Issue 1108

Priming Condensate Trap
The condensate trap should be primed with water prior to

start-up to ensure proper condensate drainage. Either pour

10 fl. oz. (300 ml) of water into the trap, or follow these

steps to prime the trap:

1. Follow the lighting instructions to place the unit into

operation.

2. Set the thermostat to initiate a heating demand.

3. Allow the burners to fire for approximately 3 minutes.

4. Adjust the thermostat to deactivate the heating demand.

5. Wait for the combustion air inducer to stop. Set the

thermostat to initiate a heating demand and again allow

the burners to fire for approximately 3 minutes.

6. Adjust the thermostat to deactivate the heating demand

and wait for the combustion air inducer to stop. At this

point, the trap should be primed with sufficient water to

ensure proper condensate drain operation.

If you do not follow these instructions exactly, a fire or

explosion may result causing property damage, personal

injury or death.

WARNING

Gas Valve Operation (Figure 57)

1. STOP! Read the safety information at the beginning of

this section.

2. Set the thermostat to the lowest setting.

3. Turn OFF all electrical power to the unit.

4. This furnace is equipped with an ignition device which

automatically lights the burners. Do not try to light the

burners by hand.

5. Remove the upper access panel.

6. Move gas valve switch to OFF. See Figure 57.

7. Wait five minutes to clear out any gas. If you then smell

gas, STOP! Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s

instructions. If you do not smell gas go to next step.

8. Move gas valve switch to ON. See Figure 57.

9. Replace the upper access panel.
10. Turn on all electrical power to the unit.
11. Set the thermostat to desired setting.

NOTE: When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.

12. If the appliance will not operate, follow the instructions

“Turning Off Gas to Unit” and call your service technician

or gas supplier.

Turning Off Gas to Unit
1. Set the thermostat to the lowest setting.

2. Turn off all electrical power to the unit if service is to be

performed.

3. Remove the upper access panel.

4. Move gas valve switch to OFF.

5. Replace the upper access panel.

Failure To Operate
If the unit fails to operate, check the following:

1. Is the thermostat calling for heat?

2. Are access panels securely in place?

3. Is the main disconnect switch closed?

4. Is there a blown fuse or tripped breaker?

5. Is the filter dirty or plugged? Dirty or plugged filters will

cause the limit control to shut the unit off.

6. Is gas turned on at the meter?

7. Is the manual main shut–off valve open?

8. Is the internal manual shut–off valve open?

9. Is the unit ignition system in lockout? If the unit locks

out again, inspect the unit for blockages.

Heating Sequence Of Operation
1. When thermostat calls for heat, combustion air inducer

starts.

2. Combustion air pressure switch proves blower

operation. Switch is factory set and requires no

adjustment.

3. After a 15 second prepurge, the hot surface ignitor

energizes.

4. After a 20 second ignitor warm-up period, the gas valve

solenoid opens. A 4-second “Trial for Ignition” period

begins.

5. Gas is ignited, flame sensor proves the flame, and the

combustion process continues.

6. If flame is not detected after first ignition trial, the ignition

control will repeat steps 3 and 4 four more times before
locking out the gas valve. The ignition control will then
automatically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60 minute period, move thermostat from
“Heat” to “OFF” then back to “Heat”. Heating sequence
then restarts at step 1.

MANIFOLD

PRESSURE

OUTLET

GAS VALVE SHOWN IN ON POSITION

INLET

PRESSURE

PORT

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

FIGURE 57

(UNDER CAP)