Page 32

Advertising
background image

506724-01

Page 32 of 57

Issue 1108

NOTE: If necessary the condensate trap may be installed

up to 5’ away from the furnace. Use PVC pipe to connect

trap to furnace condensate outlet. Piping from furnace must

slope down a minimum of 1/4” per ft. toward trap.

1. Determine which side condensate piping will exit the

unit, location of trap, field-provided fittings and length of

PVC pipe required to reach available drain.

2. Remove plug (Figure 43) from the cold end header box

at the appropriate location on the side of the unit. Install

field-provided 1/2 NPT male fitting into cold end header

box. Use Teflon tape or appropriate pipe dope.

3. Install the cap over the clean out opening at the base of

the trap. Secure with clamp. See Figure 47.

4. Install drain trap using appropriate PVC fittings, glue all

joints. Glue the provided drain trap as shown in Figure

47. Route the condensate line to an open drain.

Condensate line must maintain a 1/4” downward slope

from the furnace to the drain.

5. Install field provided vent on trap assembly as shown in

Figures 44 through 46. Trap must extend at least 1”

above the furnace condensate drain connection in upflow

applications and 4-1/2” above the bottom of the cabinet

in horizontal applications.

6. If unit will be started immediately upon completion of

installation, prime trap per procedure outlined in Unit

Start-Up section.

Do not use copper tubing or existing copper condensate

lines for drain line.

CAUTION

Condensate Piping

This unit is designed for either right or left side exit of

condensate piping in upflow applications. In horizontal

applications, the condensate trap must extend below the

unit. An 8” service clearance is required for the condensate

trap. Refer to Figure 43 for condensate trap locations.

FIGURE 43

CONDENSATE TRAP AND PLUG LOCATIONS

(Unit shown in upflow position)

NOTE − In up flow applications where side return
air filter is installed on same side as the conden-
sate trap, filter rack must be installed beyond
condensate trap or trap must be re−located to
avoid interference.

Trap

(same on

right side)

Plug

(same on left side)

1−1/2 in.