Caution – Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 33

Advertising
background image

506724-01

Page 33 of 57

Issue 1108

Do not use copper tubing or existing copper condensate

lines for drain line.

CAUTION

Condensate line must slope downward away from the trap

to drain. If drain level is above condensate trap, condensate

pump must be used. Condensate drain line should be routed

within the conditioned space to avoid freezing of condensate

and blockage of drain line. If this is not possible, a heat

cable kit may be used on the condensate trap and line.

Heating cable kit is available in various lengths; 6 ft. (1.8 m)

- kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69; and 50 ft. (15.2

m) - kit no. 26K70.

FIGURE 44

CONDENSATE TRAP LOCATIONS

(Unit shown in upflow position with remote trap)

5’ max.

To Drain

*PVC Pipe Only

Field−Provided Vent

Min. 1" Above Condensate

Drain Connection

1" Min.

Trap can be installed a

maximum 5’ from furnace.

*Piping from furnace must slope down a minimum
of 1/4" per ft. toward trap.

CAUTION

A separate drain line must be run to the drain from
the condensate trap to ensure proper drainage and
pressure switch operation. DO NOT connect the
condensate trap drain into the drain line from the
evaporator coil.

FIGURE 45

Unit with Cooling Coil

Drain

Condensate trap and

evaporator coil must

be drained separately

as shown.

Field−Provided

Vent

Drain

Field−Provided

Vent

FIGURE 46

CONDENSATE TRAP LOCATIONS

(Unit shown in horizontal right−hand discharge position)

5’ max.

to drain

*PVC Pipe Only

4−1/2"

Min.

Field−Provided Vent

Must Not Interfere With

Service To The Unit

*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.

Advertising
This manual is related to the following products: