Details of Exhaust Piping Terminations for Non-Direct

Vent Applications

Exhaust pipes may be routed either horizontally through an

outside wall or vertically through the roof. In attic or closet

installations, vertical termination through the roof is preferred.

Figures 39 through 42 show typical terminations.

1. Exhaust piping must terminate straight out or up as

shown. The termination pipe must be sized as listed in

Table 6. The specified pipe size ensures proper velocity

required to move the exhaust gases away from the

building.

2. On field supplied terminations for side wall exit, exhaust

piping may extend a maximum of 12 inches (305 mm)

for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond

the outside wall. See Figure 40.

FIGURE 35

DIRECT VENT CONCENTRIC ROOFTOP TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

Minimum

Above Average

Snow

Accumulation

SHEET METAL STRAP

(Clamp and sheet metal strap

must be field installed to support
the weight of the termination kit.)

FLASHING

(Not Furnished)

CLAMP

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

1 1/2" (38mm) accelerator

provided on 71M80 & 44W92

12” (305mm)

INTAKE

AIR

EXHAUST

VENT

12" (305mm) Min.

above grade or

average snow
accumulation.

FIGURE 36

DIRECT VENT CONCENTRIC WALL TERMINATION

71M80, 69M29 or 60L46 (US)

44W92 or 44W93 (Canada)

INTAKE

AIR

INTAKE

AIR

INTAKE

AIR

OUTSIDE

WALL

GRADE

CLAMP

(Not Furnished)

FIELD−PROVIDED

REDUCER MAY BE REQUIRED

TO ADAPT LARGER VENT

PIPE SIZE TO TERMINATION

EXHAUST

VENT

1−1/2" (38mm) accelerator

provided on 71M80 & 44W92

EXHAUST

VENT

FIGURE 37

EXHAUST

VENT

INTAKE

AIR

5−1/2"

(140mm)

Front View

12"

(305mm)

5"

(127mm)

18" MAX.

(457mm)

EXHAUST VENT

INTAKE

AIR

OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT

INSTALLATION OF DIRECT VENT WALL TERMINATION KIT

Inches (mm)

Side View

12" (305mm) Min.

above grade or

average snow

accumulation.

optional intake elbow

DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

NOTE − Do not discharge exhaust gases directly into any chimney or vent st ack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 38

3" − 8"

(76mm−

203mm)

STRAIGHT−CUT OR

ANGLE−CUT IN DIRECTION

OF ROOF SLOPE *

EXHAUST VENT

1/2" (13mm)

WEATHERPROOF

INSULATION

SHOULDER OF FITTINGS

PROVIDE SUPPORT

OF PIPE ON TOP PLATE

ALTERNATE

INTAKE PIPE

INTAKE PIPE

INSULATION (optional)

EXTERIOR

PORTION OF

CHIMNEY

INSULATE

TO FORM

SEAL

SHEET

METAL TOP

PLATE

*SIZE TERMINATION

PIPE PER TABLE 6.

Minimum 12" (305MM)

above chimney top

plate or average snow

accumulation

8" − 12"

(203mm − 305mm)

3"−8"

(76mm−203mm)