Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 44

Advertising
background image

506724-01

Page 44 of 57

Issue 1108

Natural

to

LP/Propane

LP/Propane

to

Natural

High Altitude

Natural

Burner Orifice

Kit

High Altitude

LP/Propane

Burner Orifice

Kit

All

68W75*†

73W80*

51W01

68W70*†

* Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion kit.
† LP kits includes low line pressure switch.

Unit

Size

0 - 4,500 ft

(0 - 1,373 m)

4,501 - 7,500 ft

(1,373 - 2,286 m)

7,501 - 10,000 ft

(2,286 - 3,038 m)

All

No Change

No Change

74W91

Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 7,500 feet.

Unit

Size

0 - 4,500 ft

(0 - 1,373 m)

4,501 - 7,500 ft

(1,373 - 2,286 m)

7,501 - 10,000 ft

(2,286 - 3,038 m)

045

No Change

No Change

74W90

070

No Change

77W43

73W22

090

No Change

77W42

73W22

110

No Change

77W43

73W22

135

No Change

77W42

73W22

Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 4,500 feet.

Table 12

A95 and 95G1 Pressure Switches at Varying Altitudes

0 - 7,500 ft

(0 - 2,286 m)

7,501 - 10,000 ft

(2,286 - 3,038 m)

Unit

Size

Burner Orifice Conversion Kits at Varying Altitudes

A93 and 92G1 Pressure Switches at Varying Altitudes