Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 43

Advertising
background image

506724-01

Page 43 of 57

Issue 1108

Gas Pressure Adjustment

Gas Flow (Approximate)

Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in
Table 9. If manifold pressure matches Table 10 and rate is
incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.

NOTE: To obtain accurate reading, shut off all other gas

appliances connected to meter.

Supply Pressure Measurement
When testing supply gas pressure, use the 1/8” N.P.T.

plugged tap or pressure post located on the gas valve to

facilitate test gauge connection. See figure 56. Check gas

line pressure with unit firing at maximum rate. Low pressure

may result in erratic operation or underfire. High pressure

can result in permanent damage to gas valve or overfire.

On multiple unit installations, each unit should be checked

separately, with and without units operating. Supply pressure
must fall within range listed in table 10.

Manifold Pressure Measurement

1. Remove the threaded plug from the outlet side of the

gas valve and install a field provided barbed fitting.
Connect to a manometer to measure manifold pressure.

2. Start unit and allow 5 minutes for unit to reach steady

state.

3. While waiting for the unit to stabilize, observe the flame.

Flame should be stable and should not lift from burner.

Natural gas should burn blue.

4. After allowing unit to stabilize for 5 minutes, record

manifold pressure and compare to value given in Table

9.

NOTE: Shut unit off and remove manometer as soon as

an accurate reading has been obtained. Take care to remove

barbed fitting and replace threaded plug.

Proper Combustion

Furnace should operate minimum 15 minutes with correct

manifold pressure and gas flow rate before checking

combustion. Take combustion sample beyond the flue outlet

and compare to the tables below.

High Altitude Information

NOTE: In Canada, certification for installations at elevations

over 4500 feet (1372 m) is the jurisdiction of local authorities.

Units installed at altitudes of 4,501 - 10,000 feet (1373 -
3048 m) may require a pressure switch change which can
be ordered separately.

Table 12 lists required pressure switch changes and orifice
conversion kits at varying altitudes.

The combustion air pressure switches are factory set and
require no adjustment.

TABLE 9

GAS METER CLOCKING CHART

Unit

Seconds for One Revolution

Natural

LP

1 cu ft

Dial

2 cu ft

Dial

1 cu ft

Dial

2 cu ft

DIAL

−045

80

160

200

400

−070

55

110

136

272

−090

41

82

102

204

−110

33

66

82

164

−135

27

54

68

136

Natural−1000 btu/cu ft LP−2500 btu/cu ft

TABLE 10

Supply Line and Manifold Pressure (inches w.c.)

Unit

Fuel

Manifold

Pressure

Line Pressure

All

Nat. Gas

3.5

4.5 − 10.5

All

L.P. Gas

10.0

11.0 − 13.0

NOTE − A natural to L.P. propane gas changeover kit is nec-
essary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.

TABLE 11

Unit

CO

2

%

For Nat

CO

2

%

For L.P.

7.2 − 7.9

8.6 − 9.3

The maximum carbon monoxide reading should not exceed 50 ppm.

All

Advertising
This manual is related to the following products: