9400 Technology applications | Synchronism with mark synchronisation

Parameter setting & configuration

Quick stop

4.9

Quick stop

[4-14] Basic function "Quick stop" (schematic diagram)

r

The quick stop function can be activated as follows in the Lenze setting:
– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortControl1:

By setting bit 2 of the bit-coded control word 1.

r

Parameter setting: Tab Application parameters  dialog level Overview  All basic

functions  Quick stop

The basic function "Quick stop" brakes the

drive to standstill within the deceleration

time set for the quick stop function after a

corresponding request independent of the

setpoint selection.
If the quick stop function is deactivated,

the drive is led to the selected setpoint

again via the set acceleration time.

v

t

t

M

Slave

n

t

LS_Limiter

n

t

LS_Quickstop

STOP

Parameter

Lenze setting

Value Unit

C00105

Quick stop deceleration time

0.000 s

C00106

Quick stop S-ramp time

0.00 %

C00107

Reference for quick stop deceleration time

Motor reference speed (C00011)

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DIGIN 1  Activate quick stop 1

C03135/1

Control word 1

bit 02



Activate quick stop 2

C03135/2

FALSE  Activate quick stop 3

C03135/3