Lenze E94AxHE Technology Application Synchronism User Manual

Page 68

Advertising
background image

9400 Technology applications | Synchronism with mark synchronisation

Parameter setting & configuration

Parameterisable function blocks

68

L

EDS94TA10040xxxx EN 1.1 - 10/2008

C3856

Deactivation mode

0 Positioning function deactivated:

• The position output dnPosOut_p

is set to 0.

• The status signal bInTarget is

reset to FALSE.

Lenze setting

1 Positioning function changes to the

stand-by state:

• The position output dnPosOut_p

is held on the current position

dnActPos_p.

• The status signal bInTarget is

reset to FALSE.

2 Positioning function changes to the

stand-by state:

• If bSetPosZero = FALSE:

The position output dnPosOut_p

is held on the set position

dnSetPos_p.

• If bSetPosZero = TRUE:

The position output dnPosOut_p

is held on zero.

• The status signal bInTarget is

reset to FALSE.

C03857/1

String of digits

Position unit

• Read only

C03857/2

String of digits

Speed unit

• Read only

C03858/1

0.0000

unit/t

214748.3647 Positive traversing speed

• Initialisation: 1000 unit/t

C03858/2

0.0000

unit/t

214748.3647 Negative traversing speed

• Initialisation: 1000 unit/t

C03859

-214748.3647

unit/t

214748.3647 Reference speed

• Read only (generated from the

machine parameters applied at

the input AxisData)

• Reference value for selecting

speeds.

C03861/1

0.010

s

130.000 Acceleration ramp

• Initialisation: 1.000 s

• Reference = reference speed

(display under C05054)

C03861/2

0.010

s

130.000 Deceleration ramp

• Initialisation: 1.000 s

• Reference = reference speed

(display under C05054)

C03861/3

0.010

s

130.000 Stop ramp

• Initialisation: 1.000 s

• Reference = reference speed

(display under C05054)

C03870

-2147483647

unit/t

2147483647 Speed at the output

• Display of the dnSpeedOut_s

output signal in the real unit of

the machine.

C03872

-214748.3647

unit

214748.3647 Position at the output

• Display of the dnPosOut_p output

signal in the real unit of the

machine.

Parameter

Possible settings

Information

Advertising