B-92 DeviceNet Data Tables

Instance 2 Attributes (Predefined Master/Slave Polled I/O
Message Connection)

14

Get

Produced Connection Path

Array of USINT

null (no data)

15

Get

Consumed Connection Path
Length

UINT

0

16

Get

Consumed Connection Path

Array of USINT

null (no data)

17

Get

Production Inhibit TIme

UINT

0

Attribute ID

Access Rule

Name

DeviceNet Data
Type

Data Value

Attribute ID

Access Rule

Name

DeviceNet

Data Value

1

Get

State

USINT

0=nonexistent 1=configuring
(default) 2=waiting for
connection ID 3=established
4=timed out 5=deferred delete

2

Get

Instance Type

USINT

1=I/O message

3

Get

Transport Class Trigger

Byte

0x82 or 0x83

4

Get

Produced Connection ID

UINT

01111xxxxxx
xxxxxx=node address

5

Get

Consumed Connection ID

UINT

10xxxxxx101
xxxxxx=node address

6

Get

Initial Comm Characteristics

Byte

0x01

7

Get

Produced Connection Size

UINT

8

8

Get

Consumed Connection Size

UINT

4

9

Get/Set

Expected Packet Rate

UINT

0 default

12

Get

Watchdog Timeout Action

USINT

0=timeout (default) 1=auto
delete 2=auto reset

13

Get

Produced Connection Path
Length

UINT

6

14

Get

Produced Connection Path
LogicalSegment, Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number

Array of:
USINT

0x20
0x04
0x24
0x01
0x30
0x03

15

Get

Consumed Connection Path
Length

UINT

6

16

Get

Consumed Connection Path
Logical Segment,Class
Class Number
Logical Segment, Instance
Instance Number
Logical Segment, Attribute
Attribute Number

Array of:
USINT

0x20
0x04
0x24
0x02
0x30
0x03

17

Get

Production Inhibit Time

UINT

0

Advertising