Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 49

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

DeviceNet Data Tables B-19

Instance 15 Attributes (Metering real energy results)

Assembly Structure

Common Services

Attribute ID Access

Rule

Name

DeviceNet Data Type

3

Get

Data

Structure of
32 bytes (16 Words)

Param #

Parameter name

Data type

#bytes

Master Module Range

Word No.

Range

Modulu
s

1

KWh forward

Modulus

10

0 to 1.0x10

12

1

+0 to 999

10

12

2

+0 to 999

10

9

3

+0 to 999

10

6

4

+0 to 999

10

3

5

+0 to 999

10

0

2

KWh reverse

Modulus

10

–1.0x10

12

to 0

6

–0 to 999

10

12

7

–0 to 999

10

9

8

–0 to 999

10

6

9

–0 to 999

10

3

10

–0 to 999

10

0

3

KWh net

Modulus

10

–1.0x10

12

to 1.0x10

12

11

±0 to 9999

10

12

12

±0 to 9999

10

9

13

±0 to 9999

10

6

14

±0 to 9999

10

3

15

±0 to 9999

10

0

4

Metering iteration

Int

2

Used by external device to
determine if it has new
metering data. Counts from
0 to 32767, then rolls over
to 0.

16

Service
Code

Service Name

0Ehex

Get_Attributes_Single

Advertising