Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 75

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

DeviceNet Data Tables B-45

Assembly Structure

Common Services

Param #

Parameter name

Data
type

#bytes

Master Module Range

Default
Setting

Word
No.

1

Password

Int

2

-1, 0 to 9999
Correct password is required to
configure/reconfigure harmonic Analysis
functionality, but not required to select
harmonic channel or data group to be read back
in the harmonic results data assembly. If the
user is only selecting harmonic result data to be
read, set password to –1.

0

1

2

Harmonic channel
to be read

Int

2

1 = L1 Voltage
2 = L1 Current
3 = L2 Voltage
4 = L2 Current
5 = L3 Voltage
6 = L3 Current
7 = L4 Current

2

3

Read % distortion,
magnitude, or phase
angle data

Int

2

Selects which type of data appears in Instance
39 through Instance 43 (% distortion of
harmonic, magnitude of harmonic, or phase
angle of harmonic). 0 = % distortion, 1 =
magnitude, 2 = phase angle.

3

4

Reserved

Int

2

Reserved for future enable/disable of all
harmonic calculations.

4

5

IEEE 519 max short
circuit current

Float

4

0.0 to 10,000,000.0

0

5
6

6

IEEE 519 max
demand/load
current

Float

4

0.0 to 10,000,000.0

0

7
8

Service
Code

Service Name

10

hex

Set_Attributes_Single