DeviceNet Data Tables B-93

Common Services

Instance 3 Attributes (General Explicit Server Message
Connection)

Service Code

Implemented for:

Service Name

Class

Instance

0x05

Yes

Yes

Reset

(1)

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

(1) For "Class", resets all connections to non-existent. For "Instance", resets connection timer, and if applicable changes the state from timed out to

established.

Attribute ID

Access Rule

Name

DeviceNet

Data Value

1

Get

State

USINT

0=nonexistent
1=configuring (default)
2=waiting for connection
ID 3=established 4=timed
out 5=deferred delete

2

Get

Instance Type

USINT

0=explicit message

3

Get

Transport Class Trigger

Byte

0x83

4

Get

Produced Connection ID

UINT

11101xxxxxx
xxxxxx=node address

5

Get

Consumed Connection ID

UINT

11110xxxxxx
xxxxxx=node address

6

Get

Initial Comm
Characteristics

Byte

0x33

7

Get

Produced Connection Size

UINT

0x80

8

Get

Consumed Connection Size

UINT

0x80

9

Get/Set

Expected Packet Rate

UINT

2500 msect

12

Get

Watchdog Timeout Action

USINT

1=auto delete

13

Get

Produced Connection Path
Length

UINT

6

14

Get

Produced Connection Path:
LogicalSegment, Class
Class Number
Logical Segment, Instance
Instance Number

Logical Segment, Attribute
Attribute Number

Array of:
USINT

0x20
0x04
0x24
4, 6, 8, 10-19, 21, 22,
24-28, 30, 31, 33, 34, 36,
37, 39-49 (multiple
instances supported)
0x30
0x03

15

Get

Consumed Connection
Path Length

UINT

6

Advertising