Common services, Assembly structure – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 70

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

B-40 DeviceNet Data Tables

Common Services

Instance 35 Attributes (Oscillography configuration/readback
data select)

Assembly Structure

10

Setpoint action

Int

2

0 to 20

13

11

Setpoint level (float value)

Float

4

±9999.0x10

21

If limit stored in event log is an integer, this
returns to 0.

14
15

Param #

Parameter name

Data type

#bytes

Master Module Range

Word No.

Service
Code

Service Name

0Ehex

Get_Attributes_Single

Attribute
ID

Access
Rule

Name

DeviceNet
Data Type

3

Set

Data

Structure of
18 bytes (9 Words) (when Master
Module firmware is V2.10 or earlier)
22 bytes (11 Words) (when Master
Module firmware is V3.00 or later)

Param # Parameter name

Data Type

# bytes Description

Default
Setting

Word No.

1

Password

Int

2

The correct password (0 to 9999) is required to
configure/reconfigure oscillograph functionality, but
not required to select oscillograph data to be read
back. If the user is only selecting data to be read, set
password to –1.

-

1

2

Initiate a capture

Int

2

0 = Do not initiate a capture
1 = Initiate a capture #1
2 = Initiate capture #2

1

-

2

3

Clear hold of
capture

Int

2

Effective only when Buffer Type (parameter 6) is
configured in ‘Hold’ mode.
0 = No effect
1 = Clear hold of capture #1
2 = Clear hold of capture #2

1

-

3

4

Channel to read

Int

2

Specifies the oscillograph channel to get during a
subsequent read of .
1 = Capture #1 V1 11 = Capture #2 V1
2 = Capture #1 I1 12 = Capture #2 I1
3 = Capture #1 V2 13 = Capture #2 V2
4 = Capture #1 I2 14 = Capture #2 I2
5 = Capture #1 V3 15 = Capture #2 V3
6 = Capture #1 I3 16 = Capture #2 I3
7 = Capture #1 I4 17 = Capture #2 I4
8 = Channel A
9 = Channel B

-

4