Instance 36 attributes (oscillography, Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 72

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

B-42 DeviceNet Data Tables

Instance 36 Attributes (Oscillography Configuration Read)

Assembly Structure

Common Services

Attribute ID Access

Rule

Nam
e

DeviceNet Data Type

3

Get

Data

Structure of
10 bytes (5 Words) (when Master Module firmware is
V2.10 or earlier)
14 bytes (7 Words) (when Master Module firmware is
V3.00 or later)

Param # Parameter name

Data Type

# bytes Description

Default
Setting

Word No.

1

Password

Int

2

Always returns –1

-

1

2

Buffer type

Int

2

Indicates how captures are buffered.
0 = Hold (1

st

capture is held)

1 = Overwrite (new captures overwrite existing ones)

1

2

3

Channel A

Int

2

Indicates signal for channel A when Oscillograph type =
0.
1=V1, 2=I1, 3=V2, 4=I2, 5=V3, 6=I3, 7=I4

1

3

4

Channel B

Int

2

Indicates signal for channel B when Oscillograph type =
0.
Refer to ‘Channel A’ for a list of selections.

2

4

5

Pretrigger

Int

2

-1 = No pretrig
0 to 8 = number of pre-trigger cycles

0

5

6

Oscillograph type

(1)

Int

2

0 = Master Module firmware V2.10 compatible mode
(7channel x 2 cycle + 2 channel x 12 cycle)
1 = 10.8kHz, 1 capture
2 = 10.8kHz, 2 captures
3 = 5.4kHz, 1 capture
4 = 5.4kHz, 2 captures
5 = 2.7kHz, 1 capture
6 = 2.7kHz, 2 captures

0

6

7

Overwrite
timeout

(1)

Int

2

When ‘Buffer Type’ is configured in ‘overwrite’ mode,
this parameter indicates the amount of time (in
minutes) that a capture will be held before it is cleared.
Range = 1 to 4320

1

7

(1) Available on master module firmware V3.00 or later (not implemented on previous versions)