Publication 1403-IN054A-EN-P - August 2001

Product Description 1-15

5. Edit the Data Table Map.

The DeviceNet Scanner needs to know which bytes will be
scanned from the Powermonitor II. Select the Input tab. This
allows the user to determine where the informatin is stored
inside the scanner module. When finished configuring, select the
Apply button.

6. Download Configuration to the Scanner.

All of the configuration data must be downloaded to the scanner
module. Select the Download to Scanner button, download All
Records, and all the scanner to reset.
After being reset, the DeviceNet Scanner displays an 80,
followed by the node address of the DeviceNet Scanner (00 in
this case) when everything is configured properly.

Input parameters for Powermonitor II are Instance 1 and output
parameters are Instance 2. Output parameters are reserved and
may not be written to in ladder.