Instance 13 attributes (metering power results), Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 47

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

DeviceNet Data Tables B-17

Instance 13 Attributes (Metering power results)

Assembly Structure

Common Services

Attribute ID Access

Rule

Name

DeviceNet Data Type

3

Get

Data

Structure of
50 bytes (25 Words)

Param #

Parameter name

Data type

#bytes

Master Module Range

Word No.

1

L1 real power

Float

4

0.0 to 9999x10

21

W

1
2

2

L2 real power

Float

4

0.0 to 9999x10

21

W

3
4

3

L3 real power

Float

4

0.0 to 9999x10

21

W

5
6

4

Total real power

Float

4

0.0 to 9999x10

21

W

7
8

5

L1 reactive power

Float

4

0.0 to 9999x10

21

VAR

9
10

6

L2 reactive power

Float

4

0.0 to 9999x10

21

VAR

11
12

7

L3 reactive power

Float

4

0.0 to 9999x10

21

VAR

13
14

8

Total reactive power

Float

4

0.0 to 9999x10

21

VAR

15
16

9

L1 apparent power

Float

4

0.0 to 9999x10

21

VA

17
18

10

L2 apparent power

Float

4

0.0 to 9999x10

21

VA

19
20

11

L3 apparent power

Float

4

0.0 to 9999x10

21

VA

21
22

12

Total apparent power Float

4

0.0 to 9999x10

21

VA

23
24

13

Metering iteration

Int

2

Used by external device to determine if it has
new metering data. Counts from 0 to 32767,
then rolls over to 0.

25

Service
Code

Service Name

0Ehex

Get_Attributes_Single