Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 14

Advertising
background image

Publication 1403-IN054A-EN-P - August 2001

1-8 Product Description

Table 1.4 Communication Configuration Items

Communication Parameter

Description

New Node Address

Enter the node address (0 to 64) (default is
63) of the Powermonitor II on the DeviceNet
link. A node address change takes effect on
reset.

New Baud Rate

The options are 125K, 250K, 500K, AUTO
and PGM (default is 125K). The selected
baud rate takes effect after a reset. The
maximum cable length is restricted at
higher baud rates.

Bus-Off Interrupt

Specify what occurs when a CAN bus-off
interrupt occurs in the DeviceNet network.
The Powermonitor II is not allowed network
access when Hold in Reset is selected and
a bus-off interrupt occurs. HOLD IN RESET
stops communication and waits for power
to be cycled.
RESET AND CONTINUE resets DeviceNet
communications and attempts to
re-establish the communication link.