Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 39

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

DeviceNet Data Tables B-9

Instance 6 Attributes (Basic Device Configuration Data Read)

Assembly Structure

Common Services

Attribute
ID

Access
Rule

Name

DeviceNet
Data Type

3

Get

Data

Structure of
40 bytes (20 Words)

Param #

Parameter name

Data type

#bytes

Master Module Range

Default
Setting

Word No.

1

Present unit password

Int

2

PM-II will always return –1

0

1

2

New password

Int

2

PM-II will always return –1

0

2

3

Voltage mode

Int

2

0 = Demo
1 = Single
2 = Open Delta
3 = 3-Wire Delta
4 = 4-Wire Wye
5 = Direct Delta

4

3

4

Vaux voltage mode

Int

2

0 = AC
1 = DC

0

4

5

L1/L1/L3 PT primary

Float

4

1.0 to 10,000,000.0

120.0

5
6

6

L1/L2/L3 PT secondary

Float

4

1.0 to 999.0

120.0

7
8

7

I1/I2/I3 CT primary

Float

4

1.0 to 10,000,000.0

1 or 5

(1)

9
10

8

I1/I2/I3 CT secondary

Float

4

1.0 to 999.0

1 or 5

a

11
12

9

I4 CT primary

Float

4

1.0 to 10,000,000.0

1 or 5

a

13
14

10

I4 CT secondary

Float

4

1.0 to 999.0

1 or 5

a

15
16

11

Vaux PT primary

Float

4

1.0 to 10,000,000.0

1.0

17
18

12

Vaux PT secondary

Float

4

1.0 to 999.0

1.0

19
20

(1) This value will be 1 for 1 Amp Master Module (Cat. No. 1403-MM01X) or 5 for a 5 Amp Master Module (Cat. No. 1403-MM05X)