Assembly structure common services – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 48

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

B-18 DeviceNet Data Tables

Instance 14 Attributes (Metering power factor results)

Assembly Structure

Common Services

Attribute ID Access

Rule

Name

DeviceNet Data Type

3

Get

Data

Structure of
50 bytes (25 Words)

Param #

Parameter name

Data type

#bytes

Master Module Range

Word
No.

1

L1 true power factor

Float

4

–100.0 to +100.0

1
2

2

L2 true power factor

Float

4

–100.0 to +100.0

3
4

3

L3 true power factor

Float

4

–100.0 to +100.0

5
6

4

3-phase true power factor

Float

4

–100.0 to +100.0

7
8

5

L1 displacement power factor

Float

4

–100.0 to +100.0

9
10

6

L2 displacement power factor

Float

4

–100.0 to +100.0

11
12

7

L3 displacement power factor

Float

4

–100.0 to +100.0

13
14

8

Total displacement power factor

Float

4

–100.0 to +100.0

15
16

9

L1 distortion power factor

Float

4

0.0 to +100.0

17
18

10

L2 distortion power factor

Float

4

0.0 to +100.0

19
20

11

L3 distortion power factor

Float

4

0.0 to +100.0

21
22

12

3-phase distortion power factor

Float

4

0.0 to +100.0

23
24

13

Metering iteration

Int

2

Used by external device to determine if it has
new metering data. Counts from 0 to 32767,
then rolls over to 0.

25

Service
Code

Service Name

0Ehex

Get_Attributes_Single

Advertising