Publication 1403-IN054B-EN-P - August 2001

DeviceNet Data Tables B-41

Common Services

5

Data block to get

Int

2

Specifies which portion of the capture to get during a
subsequent read of . The number of blocks per
waveform depends on the ‘Oscillograph type’
(parameter 10 in this table)
For Oscillograph type…
0: block range = 1 to 24 for channels 1 through 7
0: block range = 1 to 144 for channels 8 and 9
1: block range = 1 to 169

1

2: block range = 1 to 85

1

3: block range = 1 to 169

1

4: block range = 1 to 85

1

5: block range = 1 to 169

1

6: block range = 1 to 85

1

-

5

6

Buffer type

Int

2

Specifies how captures are buffered.
0 = Hold (1

st

capture is held)

1 = Overwrite (new captures overwrite existing ones)

1

6

7

Channel A

Int

2

Selects signal for channel A when Oscillograph type =
0.
1=V1, 2=I1, 3=V2, 4=I2, 5=V3, 6=I3, 7=I4

1

7

8

Channel B

Int

2

Selects signal for channel B when Oscillograph type =
0.
Refer to ‘Channel A’ for a list of selections.

2

8

9

Pretrigger

Int

2

-1 = No pretrig
0 to 8 = number of pre-trigger cycles

0

9

10

Oscillograph type

(1)

Int

2

0 = Master Module firmware V2.10 compatible mode
(7channel x 2 cycle + 2 channel x 12 cycle)
1 = 10.8kHz, 1 capture
2 = 10.8kHz, 2 captures
3 = 5.4kHz, 1 capture
4 = 5.4kHz, 2 captures
5 = 2.7kHz, 1 capture
6 = 2.7kHz, 2 captures

0

10

11

Overwrite
timeout

(1)

Int

2

When ‘Buffer Type’ is configured in ‘overwrite’ mode,
this parameter specifies the amount of time (in
minutes) that a capture will be held before it is cleared.
Range = 1 to 4320

1

11

(1) Available on master module firmware V3.00 or later (not implemented on previous versions)

Param # Parameter name

Data Type

# bytes Description

Default
Setting

Word No.

Service
Code

Service Name

10

hex

Set_Attributes_Single