Assembly structure – Rockwell Automation 1403-NDNET DeviceNet Communications Card Installation Instructions User Manual

Page 90

Advertising
background image

Publication 1403-IN054B-EN-P - August 2001

B-60 DeviceNet Data Tables

Instance 54 Attribute (Snapshot 3&7 parameter record)

Assembly Structure

Attribute
ID

Access
Rule

Name

DeviceNet
Data Type

3

Get

Data

Structure of
52 bytes; 26 words
Note: this table is only supported when master module
firmware is V3.00 or later

Param
#

Parameter name

Data
Type

# bytes

Description

Word
No.

1

The value of user selected parameter #1

Float

4

Range depends on the selected parameter

1

Refer to parameter 9, Instance 23.

2

2

The value of user selected parameter #2

Float

4

Range depends on the selected parameter

3

Refer to parameter 10, Instance 23.

4

3

The value of user selected parameter #3

Float

4

Range depends on the selected parameter

5

Refer to parameter 11, Instance 23.

6

4

Avg L-L Voltage (in Delta modes)

Float

4

Range = 0 to 9999x10

21

Volts

7

Avg L-N Voltage (in non-Delta modes)

8

5

Average current

Float

4

Range = 0 to 9999x10

21

Amps

9
10

6

Voltage Unbalance

Float

4

Range = 0 to 100%

11
12

7

Current Unbalance

Float

4

Range = 0 to 100%

13
14

8

Total Real Power

Float

4

Range = 0 to 9999x10

21

Watts

15
16

9

Demand VAR

Float

4

Range = 0 to 9999x10

21

VAR

17
18

10

Total True PF

Float

4

Range = -100 to 100%

19
20

11

Record Timestamp; Year

Int

8

Year

21

Record Timestamp; Month, Day

Int

Month = Value/256
Day = Remainder of Value/256

22

Record Timestamp; Hour, Minute

Int

Hour = Value/256
Minute = Remainder of Value/256

23

Record Timestamp; Seconds, hSeconds

Int

Seconds = Value/256
Hseconds = Remainder of Value/256

24

12

Snashot record # being returned

Int

2

Range 1 to 845

25

13

Unused

Int

2

0

26

Advertising