Section 5B
9/440HR CNC/Drive System

5B-55

Figure 5B.43
Recommended Connection of 3–phase Drive Power (22 kW Series C)

Customer Supplied
E–Stop Control Relay

9/440 High–resolution Power Strip

E–Stop
Connector TB1

1

7

E–Stop
status contact

(30V dc 1.4A)

Noise suppressor

Customer supplied
24V Power Supply

Output 24 V ac or
24 V dc

AC Bulletin 100–A30N x 3 (surge protector required) or
DC Bulletin 100–A30NZ x 3

Bussman FRS–R–20A (class RK-5)

600 V ac (qty 3)

Three-phase input
360 or 480V ac

Bulletin 100
Contactor Power

Noise suppressor

Other Customer Controlled
E–Stop Status Relays

Customer
Supplied
Fuse

c

c1

m

m1

m2

m3

Optional Customer Circuit

!

ATTENTION: Brake control should not be directly
released by the E-Stop status relay (or your customer
supplied E-Stop control relay). Brakes should only be
released by the PAL logic when it has determined that the
9/440HR is in full control of the servo motors and the
control is out of E-Stop. See the description of the PAL
flag $PFLT.15 for detail on how to test drive status.