Grounded vs ungrounded three phase – Rockwell Automation 8520 9/Series Hardware TAB 5 User Manual

Page 50

Advertising
background image

Section 5A
9/440 Resolver–based CNC/Drive System

5A-48

Grounded vs Ungrounded Three Phase

The 9/440 Resolver–based CNC/Drive comes from the factory set for three
phase grounded systems. If your facility uses an ungrounded three phase
360/480 volt system, you must move a jumper in the 9/440 Resolver–based
system module. This jumper will connect an internal resistor that helps
keep high voltage static, that can be typical of ungrounded three phase
systems, from building up in the system module.

Jumper Setting

Three Phase Power

J27 to J26 (factory setting)

Grounded system

J27 to GND3

Ungrounded systems

Figure 5A.35
Three–phase Jumper (Series A and B)

9/440 Resolver–based

System Module

Open cover

J26

J27

GND3

Wire Jumper