Refer to figure 2.2 for component locations, Side view, Figure 2.2 - 1 to 5 hp @ 460 vac gv3000/se drive – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual

Page 18

Advertising
background image

2-6

GV3000/SE AC Drive ControlNet Network Communication Option Board

Step 4.

Install the ControlNet Option Board in the Keypad Bracket

Refer to figure 2.2 for component locations.

Step 4.1 Remove the ControlNet option board from its anti-static wrapper.

Step 4.2 Align the key on the connector of the ControlNet option board ribbon cable

with the key on the Regulator board connector. Press the ribbon cable
connector in until it locks into position.

Step 4.3 Route the 26-conductor ribbon cable for the Current Feedback board out of

the side of the keypad bracket.

Step 4.4 Align the ControlNet option board on the four mounting tabs on the keypad

bracket. Make sure that the ribbon cable is not pinched between the keypad
bracket and the ControlNet option board.

Step 4.5 Fasten the right side of the ControlNet option board to the keypad bracket.

Use the two metal M3 screws and lock washers for grounding.

Important: You must use the lock washers to properly ground the option board.

Improper grounding of the option board can result in erratic operation of
the drive.

Figure 2.2 – 1 to 5 HP @ 460 VAC GV3000/SE Drive

Side View

Front View

Top View

ControlNet Option
Board

Regulator Board

Current Feedback

Board

Advertising