Programming the Drive

4-9

Figure 4.2 shows how the drive information maps to the drive information integer files.

4.3.4 Using the Drive Parameters Data (N10:X)

Use file N10 to access drive parameters with unscheduled data transfers. Parameters
P.000 through P.099 map to N10:0 to N10:99. The H (Volts/Hertz) and U (Vector)
parameters map to N10:100 to N10:148 and share the same element numbers.

You can access all the parameters with one MSG instruction. By specifying only a
range of words in the MSG instruction, you can change any subset of contiguous
parameters without sending a complete new copy of the file to the drive.

See chapter 5 for a complete listing of the parameters and the drive file elements to
which they are mapped.

4.3.5 Using the Drive Display Data (N11:X)

Use file N11 to access the drive display data. This file lets you access information
such as the drive fault bits, information about the motor, and the error log.

The GV3000/SE drive updates the drive display data every 100 msec. The drive
operation data is averaged over a 500 msec period. See chapter 5 for a complete
listing of the data you can access and its location.

Figure 4.2 – Drive Information Map

N10:0

N10:99

H/U.000

H/U.048

P.000

P.099

N10:100

N10:148

N11:0

N11:14

N12:0

N12:31

N20:0

N20:148

Reference

and

Feedback

Data

Drive

Display

Data

Write

Status

File in

Drive

Option

Board

Drive

Information

Unscheduled Data Transfers (MSG) Instruction

Scheduled Data Transfers