4-2

GV3000/SE AC Drive ControlNet Network Communication Option Board

4.2.1 Configuring Scheduled Data Transfers

Before the drive can communicate on the ControlNet network, you must configure its
scheduled traffic information by using some type of ControlNet configuration software.
By configuring scheduled traffic, you define how much data the drive will send, how
often the data is sent, and where the data is written to and read from (mapped) in the
programmable controller.

You must configure each drive on the ControlNet network. Table 4.2 lists the
configuration information you must enter.

Table 4.2 – ControlNet Scheduled Traffic Configuration Information

In this field:

Enter this information:

Node

Enter the drive’s node number that you defined in P.060.

Slot
Message

These fields are not used by the GV3000/SE drive.

Module

Enter GV3000/SE.

API

This field is read only.

RPI

Enter how often you want to exchange scheduled data between
the programmable controller and the drive.

Connection Type

Select “Exclusive Owner.”
The GV3000/SE does not support Multicast operation.

Input Address

Enter the programmable controller’s input file number that will
store data received from the drive (drive feedback data).

Input Size

Enter the number of words of drive feedback data that you want
the programmable controller to receive from the drive (1 to 6).
See section 4.2.3 for information about the type of data that is
sent.

Output Address

Enter the programmable controller’s output file number that will
store data sent to the drive (drive reference data).

Output Size

Enter the number of words of drive reference data that you want
the programmable controller to send to the drive (1 to 6).
See section 4.2.2 for information about the type of data that is
sent.

Status Address

Enter the programmable’s integer file number that will store the
status of the ControlNet connection to the drive.

Config Address
Config Size

These fields are not used by the GV3000/SE drive.