Setting Up the GV3000/SE Drive

3-7

Figure 3.1 – Signal Selection for Network Output Registers

3.7

Option Port: Type and Version (P.065)

Parameter P.065 displays the option type and the software version number of the
network option board. This parameter is read only over the ControlNet network.

The display format is N.vvv, where N represents the option type (1 = RMI,

2 = AutoMax network, 4 = DeviceNet network, and 5 = ControlNet network) and vvv
represents the software version number.

For example, if 5.602 is displayed, it means the drive is using the ControlNet network
option and is running software version 6.02.

3.8

Network Reference Source (P.063) and Network Trim
Reference Source (P.064)

Parameters P.063 and P.064 are not used with the ControlNet Network Option board.
Do not write to these parameters.

Network Output Register 1

Network Output Register 2

Network Output Register 3

Network Output Register 4

Network Module

P.066

P.067

P.068

0 = Motor KW
display value
.
.
.
12

0 = Motor torque
display value
.
.
.
12

0 = Output power
factor
.
.
.
12

0 = Encoder
counter (x 4)
.
.
.
12

P.069