Configuring SLC500 Applications

6-3

The communication parameters between the SLC500 and the KFC15 must be
identical. Set the DIP switches on the KFC15 according to the application. In most
cases, choose all default settings. However, the value 19200 is preferable over the
default value (1200) for Serial Port Baud Rate.

In RSLogix5000, choose Channel Configuration in the project tree and verify that the
“General” and “Chan 0-System” parameters are the same as you set on the KFC15
DIP switches.

Figure 6.2 – Channel Configuration: Chan 0-System