Figure 5.10 - select drive type: gv3000, Figure 5.11 - module properties: name selection – Rockwell Automation GV3000/SE AC Drive ControlNet Network Communication Board, M/N 2CN3000 User Manual

Page 78

Advertising
background image

5-6

GV3000/SE AC Drive ControlNet Network Communication Option Board

Step 9. To configure a GV3000 drive, select the GV300 (figure 5.10). Click OK.

Step 10. Enter a Name, Node number, and Revision number (figure 5.11). Click Next>.

Important: Electronic Keying should be set to disabled.

Step 11. The Requested Packet Interval (RPI) schedules the connection to move data to or

from the module at least this often or the connection will fail with the RPI Not Valid
error. Set this value to 5 ms or greater, and click Next> (figure 5.12).

Figure 5.10 – Select Drive Type: GV3000

Figure 5.11 – Module Properties: Name Selection

Advertising