Installation

2-13

Step 1.

Shut Down the Drive

Step 1.1 Disconnect, lock out, and tag all incoming power to the drive.

Step 1.2 Wait five minutes for the DC bus capacitors to discharge.

Step 1.3 Remove the cover by loosening the four cover screws.

Important: Read and understand the warning labels on the inside of the drive before

proceeding.

Step 2.

Verify that the DC Bus Capacitors are Discharged

Step 2.1 Use a voltmeter to verify that there is no voltage at the drive’s AC input

power terminals (R/L1, S/L2, T/L3).

Step 2.2 Ensure that the DC bus capacitors are discharged. To check

DC bus potential:

a. Stand on a non-conductive surface and wear insulated gloves.

b. Use a voltmeter to measure the DC bus potential at the DC bus power

terminals shown in figure 2.5.

Step 3.

Remove the Keypad Bracket from the Drive

Step 3.1 Record connections to the Regulator board terminal strip if they must be

disconnected to remove the keypad bracket.

Step 3.2 Use a magnetic screwdriver to remove the M4 x 10 screws that fasten the

bottom of the keypad support bracket to the drive heat sink.

Step 3.3 Spread the retaining clips on the Regulator board ribbon cable (on the right

side) to disconnect it from the Base Board.

Step 3.4 Remove the keypad bracket. Place it with the keypad down on a flat

surface. If you cannot lay it flat, tie it up to prevent damage to wiring.

Figure 2.5 – DC Bus Voltage Terminals (1 to 20 HP @ 230 VAC)

W/T3

V/T2

U /T1

+

S/L2

1 0V

1 0 COM

Motor Leads

AC Power

Input Leads

DC Bus

Volts

R/L1

T/L3

+