Rice Lake IQ 700 Configurable Weight Indicator User Manual
Page 24
20
IQ 700 Installation Manual
All serial characters in the data format are in ASCII and consist of the following default settings:
Table 3-9. Data Formats
The transmission of serial data can be initiated in either demand mode, continuous mode, or RS485. Refer to
Section 6.6 on page 48 for advanced detailed information on serial configuration options.
14. dU
Port 1 duplex
14.1
Demand print configuration in net mode
14.1Gtn
14.1nE
Three line output G-N-T
Single line, NET print
14.2oFF
14.2 1
14.2 2
14.2 3
14.2 4
No delay after CR
1 second delay after CR
2 seconds delay after CR
3 second delay after CR
4 second delay after CR
14.3
Port 1 configuration
14.3oFF
14.3 Co
14.3 dE
Port 1 disabled
Continuous output
Demand print
14.4
In full duplex 14.4
is the baud
selection for ports
1 and 2
Ports 1 and 2 baud rate
14.6 3
14.6 6
14.6 12
14.6 24
14.6 48
14.6 96
300 bps
600 bps
1200 bps
2400 bps
4800 bps
9600 bps
14.5
Port 2 configuration
14.3oFF
14.3 Co
14.3 dE
Port 2 disabled
Continuous output
Demand print
Data Formats
1 Start Bit
7 Data Bits
1 Parity Bit (Odd Parity)
1 Stop Bit
Parameter
Subparameter
Selection
Subparmeter Data
Selection
Explanation
Net/Gross
Tare
Lb/Kg Conversion
Key which affects associated parameters
Table 3-8. Parameter 14 Configuration Parameters