Optional and Advanced Features

63

If the initiating device address matches the port address of an IQ 700 listening on the RS485 network, the indicator
responds with the following format shown in Figure 8-4.

Figure 8-4. RS485 Respond Data Format

8.1.4

Port 1 Remote Serial Commands

Port 1 has a unique set of remote serial commands.

Table 8-1. Port 1 Remote Serial Commands

Response commands from
indicator:
<first line> <EOL>
<additional lines> <EOL>
<last line> <EOL>
Where EOL = <CR> or <CR> <LF>

<:> <00> <DATA DEMAND> <P> <POL> <DATA> <L/K> <G/N> <STAT> <CR>

Message

from

Slave

ASCII 13

decimal

Origin
address

Print

Polarity:

<space> = positive

< > = negative

L = pounds
K = kilograms

G = gross
N = net

Indicates status of indicator
display. Listed in order of priority.
Status characters
<D> Digital calibration
<A> Analog calibration mode
<I> Invalid data
<O> Over/Under range
<M> Scale in motion
<Z> Tare recall data on display
<X> Setpoint 1 on display
<Y> Setpoint 2 on display
<SP> Normal display

Response
commands from
indicator:

Function

Command

Description

Zero scale

<Z> <CR>

Cell must be out of motion or command is ignored and no “echo” is received
unless motion is set to off.

Gross mode

<G> <CR>

Change to gross

Net mode

<N> <CR>

Change to net

Auto tare

<T> <CR>

Cell must be out of motion or command is ignored and no “echo” is received
unless motion is set to off.
Sending auto-tare command puts scale into net mode.

Print

<P> <CR>

Cell must be out of motion or command is ignored and no “echo” is received
unless motion is set to off
Remote print command acts as a data request or in truck mode, initiates sequence

Start

<B> <CR>

A remote start command used in batch mode

Computer format

<PC> <CR>

PC and PG commands request serial output data in tis computer format
(continuous mode). There are no delays between commands and data
transmission is not inhibited for invalid data conditions as defined under demand
mode.

Computer format <PG> <CR> requests

gross data in net mode

Operating mode

<K> <CR>

<L> <CR>

Changes the unit of measure to kilograms
Changes the unit of measure to pounds

Option mode

<K> <CR>

<R> <CR>

<W> <CR>

When in the option mode:
Dumps all options as they are configured
Reads smart serial files
Writes to smart serial files

Configuration

mode

<J> <CR>

Command configuration dump